PAU-A1400S-HC – Precision Air Conditioner

PAU-A1400S-HC adalah precision air conditioner tipe air-cooling yang dirancang untuk kontrol suhu dan kelembapan secara presisi. Memiliki kapasitas pendinginan 1.200-1.400 W dan thermal capacity 2.000 W, dengan kemampuan aliran udara 3,7 / 4,8 m³/menit. Akurasi kontrol suhu ±0,2 °C (±0,1 °C saat menggunakan termometer platinum eksternal), serta kontrol kelembapan ±1,0 % RH dalam range 40-80 % RH.

Unit ini cocok digunakan di lingkungan dengan kebutuhan stabilitas tinggi seperti laboratorium atau ruang bersih.

Spesifikasi PAU-A-1400S-HC

Cooling scheme Air-cooling type
Control models Temperature and humidity control
Cooling capacity(W) 1200/1400
Thermal capacity(W) 2000
Humidity capacity(㎏/h) 5.2
Temperature control precision(℃) ±0.2 (±0.1 when platinum resistance thermometer is attached)
Temperature control range(℃) 20 to 30
Humidity control precision(%RH) ±1.0
Humidity control range(%RH) 40 to 80
Ambient temperature(℃) 20~35 (Temperature change gradient: Within 1℃/1h)
Ambient humidity(%RH) 10~85 (Humidity change gradient: within 5%RH/1h) (No condensation)
Processed air volume(m3/min) 3.7/4.8
External Dimensions(mm) H1065×W400×D715
Weight(kg) 98
Coating Color Ivory (Y22-85B semi-gloss)
Blower duct connection diameter(mm) φ100
Rated voltage(V) Three-phase, 200 VAC
Current consumption(A) 21.8/21.4(MAX)
Power consumption(W) 6300/6300(MAX)
Humidifier / water supply(ℓ/h) 5.2
Humidifier / Water supply pressure(MPa) 0.03~0.5
Humidifier / Water temperature(℃) 0~50
Humidifier / Water supply connection port 15A female socket (Rc: 1/2 inch)
Drain connection diameter 20A female socket (Rp: 3/4 inch)
Frame drain connection port diameter 1
Refrigerant(g) R134a 285g
Exhaust air volume(m3/min) 10.0/12.0
Noise (dB (A)) 1
Safety circuit / Main circuit Earth leakage breaker (30A 30mA)
Safety circuit / Blower Overcurrent relay, delay timer (3 minutes), surge absorber
Safety circuit / Compressor Low temperature operation prevention thermostat (18°C OFF, 20°C ON), overcurrent relay, motor protector (100°C OFF 80°C ON), surge absorber
Safety circuit / Heater Overheat prevention thermostat (65℃ OFF 70℃ ON), thermal fuse (99℃), surge absorber
Safety circuit / humidifier Float switch, overheat prevention thermostat (120 ℃ ± 10 ℃ OFF), Temperature fuse (119 ℃), automatic drain timer, manual drain switch, surge absorber
Output/Main unit abnormal output Normal open/no-voltage (250 VAC/3 A/resistive load)
Output / Temperature upper / Lower limit alarm Normal open/no-voltage (240 VAC/1 A/resistive load)
Output / Humidity upper / Lower limit alarm Normal open/no-voltage (240 VAC/1 A/resistive load)