PAU-A920S-HC – Precision Air Conditioner Ultra

PAU-A920S-HC adalah precision air conditioner tipe air-cooling yang dilengkapi modul humidifikasi, ideal untuk menjaga suhu dan kelembapan secara presisi dalam ruang kritis. Mampu menghasilkan aliran udara bersih 2,1-2,3 m³/menit dengan kapasitas pendinginan 550-650 W serta thermal capacity 1.000 W.

Akurasi kontrol suhu ±0,2 °C (±0,1 °C bila menggunakan termometer platinum eksternal), kontrol kelembapan ±1,0 % RH dalam rentang 40-80 % RH.

Ruang operasional antar suhu 20-30 °C dan kelembapan sekitar 10-85 % RH. Desain eksternal compact 965 × 400 × 615 mm dengan berat ±80 kg.

Spesifikasi PAU-A920S-HC

Cooling scheme Air-cooling type
Control models Temperature and humidity control
Cooling capacity(W) 550/650
Thermal capacity(W) 1000
Humidity capacity(㎏/h) 2.6
Temperature control precision(℃) ±0.2 (±0.1 when platinum resistance thermometer is attached)
Temperature control range(℃) 20 to 30
Humidity control precision(%RH) ±1.0
Humidity control range(%RH) 40 to 80
Ambient temperature(℃) 20~35 (Temperature change gradient: Within 1℃/1h)
Ambient humidity(%RH) 10~85 (Humidity change gradient: within 5%RH/1h) (No condensation)
Processed air volume(m3/min) 2.1/2.3
External Dimensions(mm) H965×W400×D615
Weight(kg) 80
Coating Color Ivory (Y22-85B semi-gloss)
Blower duct connection diameter(mm) φ75
Rated voltage(V) Three-phase, 200 VAC
Current consumption(A) 11.8/11.8(MAX)
Power consumption(W) 3200/3300(MAX)
Humidifier / water supply(ℓ/h) 2.6
Humidifier / Water supply pressure(MPa) 0.03~0.5
Humidifier / Water temperature(℃) 0~50
Humidifier / Water supply connection port 15A female socket (Rc: 1/2 inch)
Drain connection diameter 20A female socket (Rp: 3/4 inch)
Frame drain connection port diameter 1
Refrigerant(g) R134a 190g
Exhaust air volume(m3/min) 8.0/9.4
Noise (dB (A)) 2
Safety circuit / Main circuit Earth leakage breaker (20A 30mA)
Safety circuit / Blower Overcurrent relay, delay timer (3 minutes), surge absorber
Safety circuit / Compressor Low temperature operation prevention thermostat (18°C OFF, 20°C ON), overcurrent relay, motor protector, surge absorber
Safety circuit / Heater Overheat prevention thermostat (80℃ OFF 70℃ ON), thermal fuse (99℃), surge absorber
Safety circuit / humidifier Float switch, overheat prevention thermostat (120 ℃ ± 10 ℃ OFF), Temperature fuse (119 ℃), automatic drain timer, manual drain switch, surge absorber
Output/Main unit abnormal output Normal open/no-voltage (250 VAC/5 A/resistive load)
Output / Temperature upper / Lower limit alarm Normal open/no-voltage (240 VAC/1 A/resistive load)
Output / Humidity upper / Lower limit alarm Normal open/no-voltage (240 VAC/1 A/resistive load)