PAU-A920S-HC – Precision Air Conditioner Ultra
PAU-A920S-HC adalah precision air conditioner tipe air-cooling yang dilengkapi modul humidifikasi, ideal untuk menjaga suhu dan kelembapan secara presisi dalam ruang kritis. Mampu menghasilkan aliran udara bersih 2,1-2,3 m³/menit dengan kapasitas pendinginan 550-650 W serta thermal capacity 1.000 W.
Akurasi kontrol suhu ±0,2 °C (±0,1 °C bila menggunakan termometer platinum eksternal), kontrol kelembapan ±1,0 % RH dalam rentang 40-80 % RH.
Ruang operasional antar suhu 20-30 °C dan kelembapan sekitar 10-85 % RH. Desain eksternal compact 965 × 400 × 615 mm dengan berat ±80 kg.
Spesifikasi PAU-A920S-HC
| Cooling scheme | Air-cooling type |
|---|---|
| Control models | Temperature and humidity control |
| Cooling capacity(W) | 550/650 |
| Thermal capacity(W) | 1000 |
| Humidity capacity(㎏/h) | 2.6 |
| Temperature control precision(℃) | ±0.2 (±0.1 when platinum resistance thermometer is attached) |
| Temperature control range(℃) | 20 to 30 |
| Humidity control precision(%RH) | ±1.0 |
| Humidity control range(%RH) | 40 to 80 |
| Ambient temperature(℃) | 20~35 (Temperature change gradient: Within 1℃/1h) |
| Ambient humidity(%RH) | 10~85 (Humidity change gradient: within 5%RH/1h) (No condensation) |
| Processed air volume(m3/min) | 2.1/2.3 |
| External Dimensions(mm) | H965×W400×D615 |
| Weight(kg) | 80 |
| Coating Color | Ivory (Y22-85B semi-gloss) |
| Blower duct connection diameter(mm) | φ75 |
| Rated voltage(V) | Three-phase, 200 VAC |
| Current consumption(A) | 11.8/11.8(MAX) |
| Power consumption(W) | 3200/3300(MAX) |
| Humidifier / water supply(ℓ/h) | 2.6 |
| Humidifier / Water supply pressure(MPa) | 0.03~0.5 |
| Humidifier / Water temperature(℃) | 0~50 |
| Humidifier / Water supply connection port | 15A female socket (Rc: 1/2 inch) |
| Drain connection diameter | 20A female socket (Rp: 3/4 inch) |
| Frame drain connection port diameter | 1 |
| Refrigerant(g) | R134a 190g |
| Exhaust air volume(m3/min) | 8.0/9.4 |
| Noise (dB (A)) | 2 |
| Safety circuit / Main circuit | Earth leakage breaker (20A 30mA) |
| Safety circuit / Blower | Overcurrent relay, delay timer (3 minutes), surge absorber |
| Safety circuit / Compressor | Low temperature operation prevention thermostat (18°C OFF, 20°C ON), overcurrent relay, motor protector, surge absorber |
| Safety circuit / Heater | Overheat prevention thermostat (80℃ OFF 70℃ ON), thermal fuse (99℃), surge absorber |
| Safety circuit / humidifier | Float switch, overheat prevention thermostat (120 ℃ ± 10 ℃ OFF), Temperature fuse (119 ℃), automatic drain timer, manual drain switch, surge absorber |
| Output/Main unit abnormal output | Normal open/no-voltage (250 VAC/5 A/resistive load) |
| Output / Temperature upper / Lower limit alarm | Normal open/no-voltage (240 VAC/1 A/resistive load) |
| Output / Humidity upper / Lower limit alarm | Normal open/no-voltage (240 VAC/1 A/resistive load) |