PCU-F7000 Flexible Chiller

PCU-F7000 adalah chiller non-freon pumpless & tankless dari Apiste. Dengan kapasitas pendinginan 5.700 / 6.700 W dan kestabilan suhu ±0,1 °C, unit ini mendukung kisaran aliran air sirkulasi 10-60 L/min (flow tetap 30 L/min). Dirancang untuk air bersih atau larutan glikol/ethylene glycol 15 wt% atau kurang, dengan ukuran kompak H997×W400×D600 mm dan bobot ~73 kg.

Ideal untuk integrasi ke sistem sirkulasi cairan yang sudah ada, meminimalkan ruang & pemeliharaan sambil menjaga performa yang stabil.

Spesifikasi PCU-F7000 Flexible Chiller

Cooling scheme Air-cooling type
Cooling capacity (W) *1 5700 / 6700
Circulated water *2 Clean water, Ethylene glycol solution (concentration 15 wt% or less), Propylene glycol solution (concentration 15 wt% or less)
Temperature stability (℃) *3 ±0.1
Use Area Temperature (℃) 5 to 45
Temperature control / Fixed system Control target *4 : Outlet liquid temperature or External temperature sensor measurement value
Range[℃] : 5 to 40
Temperature control / Synchronized system Reference *4 : External temperature sensor measurement value
Control target : Outlet liquid temperature
Synchronization range [℃] : -10.0 to +10.0 relative to the reference temperature (factory default setting: 0.0)
Circulated water flow rate range (L/min) 10 to 60
Circulating water fixed flow rate (ℓ/min) 30/30
Circulating water maximum operating pressure (MPa) 1
Dimensions (mm) *5 H997×W400×D600
Coating Color Munsell N-87
Weight (kg) Approx. 73
Casters (Φmm×unit) 50×4
Rated Voltage (V) *6 Three-phase, 200V AC / 200 to 220V AC (50/60Hz)
Power Consumption (kW) *1 1.8 / 2.3
Current consumption (A) *1 7.4 / 7.8
Recommended breaker capacity (A) 20
Circulating water inlet / outlet port size Rc3/4
Drain discharge port size G1/2
Components / Compressor Fully sealed rotary type
Components / Condenser Parallel flow condenser
Components / Evaporator Structure : Plate-type heat exchanger
Material : SUS316 (copper brazing)
Refrigerator R1234yf 725g
Noise (dB) *7 57 / 65
Safety circuit / Compressor Thermal protector, electromagnetic switch
Safety circuit / Fan motor Thermal protector, current fuse
Input / Alarm output No voltage, normally open (maximum 250V AC and 1 A/30 V DC and 2A)
Input/Output / Water temperature upper / lower limit output No voltage, normally open (maximum 250V AC and 1 A/30 V DC and 2A)
Input/Output / Operation stop output No voltage, normally open (maximum 250V AC and 1 A/30 V DC and 2A)
Input/Output / Emergency stop input No-voltage input
Input/Output / Operation stop input No-voltage input
Input/Output / Error reset input No-voltage input
Input/Output / External temperature sensor *7 Pt100